Phase | Three Phase |
Frequency | 50 Hz |
Winding Material | Copper/Aluminium |
Ratings | Upto 200 kVA |
Primary voltage | Upto 11000 V |
Secondary Voltage | 433 V |
Temperature Rise | 35 C / 40 C |
Star Rating Distribution Transformers with Energy efficiency level 2 as per IS 1180:2014 (Part I)
- Maximum Ambient Temperature=45°C
- Oil temperature Rise: 35°C
- Winding Rise: 40°C
- Tap switch: NIL(For 16 KVA to 100 KVA)
- Type Of Winding Aluminum wound Off circuit Tap switch: +5% to -5% @ 2.5%(For 160 & 200 KVA)
- TOC (Total Owning cost) = IC+ (A X Wi ) +(B X Wc)
- IC = Initial cost (unit end cost without tax) of transformer as quoted by the bidder.
- Wi = No Load losses quoted by the bidder in WattWc = Full load losses at 75 °C quoted by the bidder in Watt
- A Factor = Cost of no load losses in Rs/ WattB Factor = Cost of full load losses at 75 °C in Rs. / Watt
Distribution Transformer in KVA | Level 1 rated Transformer | Level 2 rated Transformer | ||
*Total loss in watts at 100 % loading should not be lower than | *Total loss in watts at 100 | *Total loss in watts at 100 % loading should not be lower than (Not equal to) | *Total loss in watts at 100 | |
5 | 95 | 115 | 75 | 95 |
10 | 240 | 270 | 215 | 240 |
16 | 440 | 480 | 400 | 440 |
25 | 635 | 695 | 595 | 635 |
63 | 1140 | 1250 | 1050 | 1140 |
100 | 1650 | 1800 | 1500 | 1650 |
200 | 2300 | 2700 | 2100 | 2300 |
500 | 4300 | 4750 | 4100 | 4300 |
Rating of Transformer in KVA | Percentage Impedance at 750C |
5 KVA | 4.00 % |
10 KVA to 100 KVA | 4.50 % |
200 KVA & 500 KVA | 4.75% |
Temperature Rise | 5 KVA | 10 to 500 KVA | |||
Top oil temperature | rise | measured | by | 30 deg.C | 35 deg.C |
Winding temperature | rise | measured | by | 35 deg.C | 40 deg.C |
- Measurement of winding resistance (at all taps if applicable) [IS2026 (Part1)].
- Measurement of voltage ratio, polarity, phase sequence and vector group[IS2026(Part1)].
- Measurement of short-circuit impedance (principal tapping, when applicable)
- Load losses at rated current and normal frequency,at50 % and100 % load [IS2026(Part1)].
- Measurement of no-load loss and current [IS2026(Part1)].
- Measurement of insulation resistance [IS2026(Part1)].
- Induced over-voltage withstand test[IS2026 (Part3)].
- Separate-source voltage withstand test [IS2026(Part3)].
- Pressure and vacuum test(as per IS: 1180-2014).
- Oil leakage test(as per IS: 1180-2014).
- Neutral current measurement, shall not be more than 2% of full load current (CEA Guideline 2008 clause no 34.9)
- Oil samples (one sample per lot) to comply with IS 1866.
- Measurement of no load losses and magnetizing current at rated frequency and at 90%, 100%and 112.5% voltage
In revised IS specification, losses for each rating for each category have been defined in three levels which are denoted by as follows;
- a) Energy Efficiency Level 1
- b) Energy Efficiency Level 2
- 3) Energy Efficiency Level 3
In each level maximum losses (No Load Loss + Load Loss) at 50% load & 100% load have been specified for each rating in all categories.
a) Three phase distribution transformers upto and including 200KVA, 11KV Class
Sl. No. | Rating (KVA) | % Z | Energy Efficiency Level 1 | Energy Efficiency Level 2 | ||
@ 50% | @ 100% | @ 50% | @ 100% | |||
1 | 16KVA | 4.5% | 150W | 480W | 135W | 440W |
2 | 25KVA | 4.5% | 210W | 695W | 190W | 635W |
3 | 63KVA | 4.5% | 380W | 1250W | 340W | 1140W |
4 | 100KVA | 4.5% | 520W | 1800W | 475W | 1650W |
5 | 160KVA | 4.5% | 770W | 2200W | 670W | 1950W |
6 | 200KVA | 4.5% | 890W | 2700W | 780W | 2300W |
b) Three phase distribution transformers Higher than 200KVA upto and including 2500KVA, 11KV Class
Sl. No. | Rating (KVA) | % Z | Energy Efficiency Level 1 | Energy Efficiency Level 2 | ||
@ 50% | @ 100% | @ 50% | @ 100% | |||
1 | 250KVA | 4.5% | 1050W | 3150W | 980W | 2930W |
2 | 315KVA | 4.5% | 1100W | 3275W | 1025W | 3100W |
3 | 400KVA | 4.5% | 1300W | 3875W | 1225W | 3450W |
4 | 500KVA | 4.5% | 1600W | 4750W | 1510W | 4300W |
5 | 630KVA | 4.5% | 2000W | 5855W | 1860W | 5300W |
6 | 1000KVA | 5.0% | 3000W | 9000W | 2790W | 7700W |
7 | 1250KVA | 5.0% | 3600W | 10750W | 3300W | 9200W |
8 | 1600KVA | 6.25% | 4500W | 13500W | 4200W | 11800W |
9 | 2000KVA | 6.25% | 5400W | 17000W | 5050W | 15000W |
10 | 2500KVA | 6.25% | 6500W | 20000W | 6150W | 18500W |
Sl. No. | Rating (KVA) | % Z | Energy Efficiency Level 1 | Energy Efficiency Level 2 | ||
@ 50% | @ 100% | @ 50% | @ 100% | |||
1 | 5KVA | 4.0% | 40W | 115W | 35W | 95W |
2 | 10KVA | 4.0% | 70W | 190W | 60W | 170W |
3 | 16KVA | 4.0% | 95W | 265W | 82W | 224W |
4 | 25KVA | 4.0% | 125W | 340W | 110W | 300W |
- a) For transformers having voltage class above 11KV and upto and including 22KV, the permissible total loss value shall not exceed by 5% of the maximum total losses values mentioned in table a) & b) for three phase.
- b) For transformers having voltage class above 22KV and upto and including 33KV, the permissible total loss value shall not exceed by 7.5% of the maximum total losses values mentioned in table a) & b) for three phase.
- c) For transformers having voltage class above 11KV and upto and including 22KV, the permissible total loss value shall not exceed by 7.5% of the maximum total losses values mentioned in table c) for single phase.
- d) For transformers having voltage class above 22KV and upto and including 33KV, the permissible total loss value shall not exceed by 10% of the maximum total losses values mentioned in table c) for single phase.